ABB Infi 90/Net90
When migrating Bailey INFI 90/NET 90 systems with SIMATIC PCS 7 V6.1, existing "Bailey consoles" are replaced by operator systems (Single Stations or Client/Server systems) based on SIMATIC PCS 7 V6.1. Existing Bailey controller configurations remain unchanged. The OS Single Stations and the OS Servers of such PCS 7/90 operator systems can be operated in redundant or individual mode. The Bailey Plant Loop/INFI-NET is connected in each case to a PCS 7/90 Operator Station (Single Station/Server) via a Computer Interface Unit (CIU) with serial RS 232 or SCSI interface.
The Database Automation (DBA) software is used for engineering of the PCS 7/90 OS stations. The data source for DBA is the Bailey Engineering Workstation with Composer or WinTools.